Wassergekühlte Doppelbodenplatte

Consisting of two heat exchangers and four EC-fans with a free cross section of 44%, the panels can be placed in the hot or cold aisle, pulling or pushing the air. Certified according to DIN EN 12825 for load capacities of 3 – 5 kN.

To avoid static charges the raised floor panels are coated with conductive powder. Existing fl oors can quickly, easily and fl exibly be changed. Depending on the spread of the fl ow temperature on water and air side, benefi ts up to 50 kW are possible.

The panel is also available as direct evaporator version. The fans react automatically on temperature changes in server cabinets and lower or raise the volume of air in dependence of preset temperature values.

The regulation of the Hydrologic V plate is done individually using the built-in control. The Hydrologic Panel can be equipped with the same coverings as the rest of the raised floor.

  • Water-chilled raised floor tile for heat dissipation in data centers with V-shaped heat exhcanger execution
  • Suitable for the usual raised floor 600 x 600 mm grid
  • 10 KW heat dissipation capacity
  • Minimal void height raised floor 600 mm
  • Can be installed in all standard raised floors
  • Suitable for new data centers or for retrofitting in existing data centers
  • Can be placed sucking in hot aisle or pressing in cold aisle
  • Condense water management possible
  • Control via target temperature or pressure
  • Optimal, energy-efficient heat dissipation up to 30 KW per rack
  • Different heights and capacities available
  • Scalable – easy exchange of raised floor panels for active panels
  • No waste of white space
  • In addition to existing CRAC/CRAH Hydrologic Panels can be placed into the hot aisle

We have prepared an interactive 3D model. You can take a closer look at a Hydrologic Panel here.

Klicken Sie auf den unteren Button, um den Inhalt von p3d.in zu laden.

Inhalt laden

PHA+PGlmcmFtZSBzcmM9Imh0dHBzOi8vcDNkLmluL2UvSDJ2SWMrc2hhZGluZyxmcyxsaW5rLWhpZGRlbiIgd2lkdGg9IjQwMCIgaGVpZ2h0PSIzNDAiIGZyYW1lYm9yZGVyPSIwIiBzZWFtbGVzcz0iIiBhbGxvd2Z1bGxzY3JlZW49ImFsbG93ZnVsbHNjcmVlbiI+PC9pZnJhbWU+PC9wPg==

Panel

Admeasurement600 x 1200 mm
Thickness535 mm, without cover
TopsidePVC, HPL, rubber
Bottomside4 x EC-Fan
Weight80 kg
MaterialPowder-coated steel
Building material classA1
Free air outlet44%
Resistance to ground< 10⁸ Ohm (Depends on coverings)

Performance

Cooling capacity40 kW
Voltage230 V
Power consumption720 W
Spread water12°C/18°C
Water volume5,5 m³/h
Air supply temprature Server21° – 30°C
Max Pressure16 bar
Pressure loss1 bar max
Cooling mediaWater or glycole water mix

Load bearing capacity

Point load3kN
Ultimate load>6kN
Heights600 – 2000 mm